General:
VD4 high-voltage indoor vacuum circuit breaker is applicable for three-phase AC power system of rated voltage up to 36kV and frequency 50/60HZ, widely used in many fields such as power plant, transformer substation, petrol chemical industry , metallurgy , manufacturing industry , airport, residential area, etc.,to control and protect the electric equipment, especially , It is used for the occasion that needs infrequent operation at rated current or multi-breaking short circuit current, may be mounted in the indoor air insulating switchgear like type KYN61 or AMS, ABB type ZS3.2 series, etc. This circuit breaker is made with mature APG technology. The application of VD4 terminal buffer guarantees the indoor terminal is ever more reliable in nay operation environment. VD4 can fully meet the requirement of GB, DL, IEC, DIN, VDE as well as standards of other advanced industrial countries.
Service environment:
a) Air temperature: Maximum temperature: +40℃; Minimum temperature:-25℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90%.
c) Altitude above sea level: Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
No
|
Item
|
Unit
|
Parameter
|
1
|
Rated voltage
|
kV
|
36
|
2
|
Rated f requency
|
Hz
|
50/60
|
3
|
Rated current
|
A
|
630, … 2500A
|
4
|
1min Power f requency withstand voltage
|
kV
|
95
|
1 18
|
5
|
Lightning impulse withstand voltage
|
kV
|
185
|
215
|
6
|
Rated short circuit breaking current (peak)
|
kA
|
50/63/80
|
7
|
Rated short breaking current
|
kA
|
20, …31.5
|
8
|
Rated short circuit making current (peak)
|
kA
|
50/63/80
|
9
|
Rated cable(line) charging breaking current
|
A
|
50 and 10
|
10
|
Rated single capacitor bank switching current
|
A
|
400
|
11
|
Rated withstand current (peak)
|
kA
|
50/63/80
|
12
|
Short time withstand current (4s)
|
kA
|
20, …31.5
|
13
|
Mechanism life
|
times
|
10000
|