General
HR4 type high voltage indoor SF6 gas circuit breaker with two installation way by drawable/Fixed. which is widely application for three-phase AC power system of rated voltage from 3.3kV up to 36kV at frequency 50/60Hz, especially using for power plant, transformer substation, petrol chemical industry, metallurgy, manufacturing industry, airport, residential area, etc..
Its high performance switchgear which will reduce over-voltage and harmonic impulse at max for by a normal or fault breaking or making.
Its easy for interchange for VD4,SF1,HD4 type switchgear like type KYN28 or AMS, ABB type ZS1 series, etc.
This circuit breaker is follow per standards like:
IEC62271-100AC high voltage circuit breaker,
GB1984-2003 AC high voltage circuit breaker
JB3855 3.6-40.5Kv indoor AC High voltage circuit breaker
DL/T403 Specification of 12-40.5kV indoor High voltage vacuum circuit breaker.
Offering
Autopuffer breaking technique
Electric arc extinction without chopped current
No restriking after breaking
Rapid recovery of the dielectric properties of the means of extinction
Withstand insulation voltage even at zero relative pressure (*)
Breaking up to 30% of the rated breaking capacity even at zero relative pressure (*)
Sealed-for-life poles
Test for checking gas tightness carried out three times on each piece of apparatus
Compact dimensions
Fixed and withdrawable version
Stored energy operating mechanism with anti-pumping device as standard common
to the whole circuit-breaker series
Mechanical safety locks against incorrect operations
Simple personalisation thanks to a com- plete range of accessories
Maintenance-free
SF6 gas pressure control device (on request).
Fields of application
HM4 circuit-breakers are used in power distribution to control and protect lines, transformer and distribution substations, motors, transformers, capacitor banks, etc.
Thanks to the SF6 autopuffer breaking technique,the HM4 circuit-breakers do not generate operating overvoltages, and are therefore also highly suitable for retrofitting, upgrading and enlarging older installations where the motor, cable, etc. insulating materials may be particularly sensitive to dielectric stresses.
Breaking technique
The breaking technique of HD4 circuit-breakers is based on compression and self-blast techniques to obtain top performances at all service current values, with minimum arc times, gradual arc extinction without chopping, and no restriking or operating overvoltages.
The HM4 series brings to medium voltage the advantages of the “autopuffer” breaking technique already used in high voltage.
Standards and approvals
HM4 circuit-breakers comply with IEC 62271-100, CEI 17-1 file 1375 Standards and with those of major industrialised countries.
They have undergone the following tests and guarantee safety and reliability of the apparatus in service in all installations.
Type tests: heating, withstand insulation at industrial and impulse frequency, short-time and peak withstand current, mechanical duration, making and breaking of short-circuit currents;
Individual tests: insulation with voltage at industrial frequency in the main circuits and insulation of the auxiliary and control circuits, measurement of the main circuit resistance, mechanical and electrical operation.
The HM4 circuit-breakers are tested according to the requirements of the IEC 62271-100 Standard (class E2 - table 21) and guarantee suitability for use in overhead lines, with rapid reclosing cycle. Labels: HD4/R sf6 circuit breaker SF1 Sf6 circuit breaker Indoor lateral sf6 circuit breaker China indoor Sf6 circuit breaker manufacturer
SF6 circuit-breaker |
|
HM4-12 |
HM4-17 |
HM4-24 |
HM4-36 |
HM4-40 |
Standards |
|
IEC 62271-100 CEI 17-1 (file 1375) |
Rated voltage |
Ur [kV] |
12 |
17.5 |
24 |
36 |
40.5 |
Rated insulation voltage |
Us [kV] |
12 |
17.5 |
24 |
36 |
40.5 |
Withstand voltage at 50 Hz(1min) |
Ud [kV] |
28 |
38 |
50 |
70 |
95 |
Impulse withstand voltage |
Up [kV] |
75 |
95 |
125 |
170 |
185 |
Rated frequency |
Fr [Hz] |
50/60 |
Rated normal current (40 °C) |
Ir [A] |
630/800/1250/1600/2000/2500/3150/3600 |
Rated breaking capacity |
Isc [kA] |
12.5/16/25/31.5/40/50 |
Rated short-time |
Ik [kA] |
12.5/16/25/31.5/40/50 |
Making capacity |
Ip [kA] |
31.5/40/50/63/80/100/125 |
Operation sequence |
|
O-0.3s-CO-15s-CO |
Opening time |
[ms] |
45 |
45 |
45 |
45 |
45 |
Arcing time |
[ms] |
10~15 |
10~15 |
10~15 |
10~15 |
10~15 |
Total breaking time |
[ms] |
55~60 |
55~60 |
55~60 |
55~60 |
55~60 |
Closing time |
[ms] |
80 |
80 |
80 |
80 |
80 |
Maximum overall dimensions |
H [mm] |
640 |
649 |
818 |
730/1060 |
790/1123 |
W[mm] |
493 |
618 |
730 |
880/955 |
748/805 |
D [mm] |
496 |
496 |
620 |
695 |
833 |
Pole centre distance |
I [mm] |
150 |
210 |
275 |
350 |
275 |
Weight |
[kg] |
114 |
114 |
119 |
128 |
190 |
Absolute SF6 gas pressure |
[kPa] |
380 |
380 |
380 |
380 |
450 |
Operating temperature |
[°C] |
-5~+40 |
Tropicalization |
|
IEC: 60068-2-30, 60721-2-1 |
Electromagnetic compatibility |
|
IEC: 60694 |